CCS Products CTS-2000-600
Split-Core Current Transformer, 600A, 2 in. Window
CTS2000600
CTS-2000-600
CCS Products CTS-2000-600
Split-Core Current Transformer, 600A, 2 in. Window
CTS2000600
CTS-2000-600
- Rated Current: 600A
- Max Current: 2000A
- 2 in. window
Log in for member pricing
- Rated Current: 600A
- Max Current: 2000A
- 2 in. window
- Accuracy: 1% from 10% to 130% of rated current
- Line Frequency: 50 to 60 Hz
- Output Voltage at Rated Amps: 0.33333 Vac
- Operating Temperature: -20°C to +55°C
- Integral burden resistor, no shorting block needed
- Core Material: silicon-iron
- Standard Lead Length: 8 ft, 22 AWG twisted pair, 600 Vac
- Split-core with removeable leg
- UL Recognized
- CE, RoHS compliant
The CCS Products CTS-2000-600 Split-Core Current Transformer, 600A, 2 in. Window features a removable section, so that it can be installed without interrupting the circuit. It has a rectangular window opening of 2″ x 2″ and offeres a rated current of 600A. The CTS series CTs do not require shorting blocks because they contain an internal secondary burden resistor, so there is no possibility of high voltage on the secondary. The internal burden resistor converts the secondary current (mA) into a safe 0.333 Vac output. CTS CTs are intended for energy monitoring with accuracies of 1% of reading from 10% to 130% of rated current.
Brand | CCS Products |
---|---|
Condition | NEW |
- 1 - Split-Core Current Transformer