CCS Products RWNC-3D-480-FT10-L
Wattnode LonWorks Meter, 480 VAC Line to Line, Revenue Model, Datalogging
CCS Products RWNC-3D-480-FT10-L
Wattnode LonWorks Meter, 480 VAC Line to Line, Revenue Model, Datalogging
- Brand Name: CCS Products
- Condition: NEW
- VAC line to line: 480
- Electrical service types: 3-Phase 3-Wire Delta 480V (No neutral), 3-Phase 4-Wire Wye 277/480V
- Measurements: Net Real Energy: kilowatt-hours (phase A, B, C, sum of all phases), Positive Real Energy: kilowatt-hours (phase A, B, C, sum of all phases), Bidirectional Real Power: Watts (phase A, B, C, and sum of all phases), Reactive Power: VARs (phase A, B, C, and sum of all phases), Power Factor: PF (phase A, B, C, all phases), Reactive Energy: kVAR-hours (sum of all phases), AC Frequency, RMS Voltage: (phase to neutral A, B, C), Computed RMS Current: (phase A, B, C), Demand kW, Peak Demand kW
- Meets accuracy requirements of ANSI C12.1 standard
- Supports LonWorks TP/FT-10 twisted-pair free topology network using Echelon's® LonTalk® (ANSI/CEA-709.1-B-2002) network protocol
- LonMark® 3.4 Certified
- Pluggable screw terminals for easy wiring
- True RMS power even with leading or lagging power factor and chopped or distorted waveforms
- Measure variable speed motor drives used in HVAC, refrigeration, and pumping systems
- Line powered
- Operating Voltage Range: -20% to +15% of the nominal rated voltage
- Power Line Frequency: 50 or 60 Hz
- Includes data logging option
- Logged values are: Date and Time, Net Energy (A, B, C and Sum), Reactive Energy (Sum), Positive Energy (Sum), Real and Reactive Power (A, B, C and Sum), Voltage, Current and Power Factor (A, B, C), Demand
- Data logging model is for special applications where LonTalk network is not available or not reliable
The CCS Products RWNC-3D-480-FT10-L Wattnode LonWorks Meter, 480 VAC Line to Line, Revenue Model, Datalogging is a networked energy meter that measures both energy consumed and energy produced (bidirectional). It provides electrical measurements such as energy (kWh), power (kW), voltage, current, kW demand, kVAR, kVARh, power factor, line frequency, etc. These measurement values are communicated using the LonTalk® communication protocol as individual phase measurements and sum or average readings. Measurements are transmitted as Standard Network Variable Types (SNVTs) through a LonWorks gateway.
Revenue-grade accuracy requires the use of current transformers with class 0.6 or better accuracy. The ACTL series of current transformers are available with class 0.6 or class 0.3 accuracy; these CTs are ideal for revenue-grade applications such as tenant billing, Solar Renewable Energy Credit (SREC), and utility revenue-grade requirements.
The WattNode meter's compact size permits installation inside most electrical service panels, junction boxes, and OEM equipment. The WattNode LonWorks meter is line-powered and does not require a separate power source.
The data logging model provides internal logging to non-volatile memory. Logging intervals can be selected from 1 minute to 12 hours. Memory allows logging of up to 250 days of 15-minute data.