Fluke 378 FC

True-RMS Non-Contact Voltage Clamp Meter with Fluke Connect Compatibility, iFlex and PQ Indicator, 1000A AC/DC

378FC
378 FC
5111812

Fluke 378 FC

True-RMS Non-Contact Voltage Clamp Meter with Fluke Connect Compatibility, iFlex and PQ Indicator, 1000A AC/DC

378FC
378 FC
5111812

The Fluke 378 FC is a True-RMS Non-Contact Voltage Clamp Meter that gives users accurate voltage and current measurements through the clamp jaw and includes an iFlex probe and PQ Indicator.

  • Power quality test provides indicates incoming power or equipment problem
  • Power quality indicator shows faulty equipment or power lines
  • Faster, safer testing without touching live wires with FieldSense
  • Measure AC current as high as 2500 A with iFlex probe
This product is available for shipping to the US, Canada, and Puerto Rico only.
$799.95 Price $888.99
This item ships FREE
In stock: 1 Units
  • Power quality test provides quick indication of whether incoming power or equipment problem exists
  • Measure voltage and current with clamp jaw
  • Power quality indicator shows whether equipment or power line is faulty
  • Faster, safer testing, all without touching live wires using FieldSense™ technology
  • No more hand-written notes or complicated math
  • Complete 3-phase voltage and current tests in 3 easy steps
  • Full set of phase-to-ground and phase-tophase values calculated
  • Displayed on smart phones and saved to cloud via Fluke Connect software
  • Phase rotation calculated and shown on Fluke Connect software
  • Measure AC current as high as 2500 A with iFlex™ probe
  • iFlex probe provides access to large conductors in tight spaces
  • Display turns green when stable Field-Sense measurement is detected
  • Visual Continuity provides bright green screen for easy detection of continuity in noisy work areas
  • TPAK magnetic hanging kit, with 9 inch (23 cm) hanging strap, lets users hang clamp wherever needed - to steel cabinet doors; around pipes; or on nail or screw heads
  • Included carrying case holds clamp, iFlex probe, test leads and black grounding clip

Fluke Connect Mobile App

  • With Fluke Connect software users can remotely log, trend and monitor measurements to pinpoint intermittent faults
  • Fluke Connect also allows users to gather data as basis for preventive maintenance programs
  • AutoRecord measurements: Take measurements automatically and instantly save them to phone; wirelessly save measurements to Fluke Cloud and add text or audio annotations
  • TrendIt graphs: Trend measurements from single session in time series graph
  • ShareLive video call: View live tool measurements, video and audio to collaborate in real time with entire team, without leaving field
  • Fluke Cloud storage: Securely store up to 5 GB of data securely, per user
  • Reports: Create reports with accurate and traceable maintenance data

Applications

  • Electricians
  • Electrical contractors
  • HVAC technicians
  • Field service engineers
  • Maintenance technicians

General Specifications

  • General maximum voltage: (between any terminal and earth ground): 1000 V
  • Battery type: 2 AA IEC LR6 alkaline
  • Battery life: 200 hours
  • Display: Dual readout
  • Automatic power off: 20 minutes
  • Jaw opening: 34 mm
  • Flexible current probe diameter: 7.5 mm
  • Flexible current probe cable length (head to electronics connector): 1.8 m
  • Rogowski coil length: 450 mm

AC Current: Jaw

  • Range: 999.9 A
  • Resolution: 0.1 A
  • Accuracy: 2 % ± 5 digits (10 Hz to 100 Hz); 2.5 % ± 5 digits (100 Hz to 500 Hz)
  • Crest factor:
    • (50/60 Hz) 3 @ 500 A
    • 2.5 @ 600 A
    • 1.42 @ 1000 A
    • Add 2 % for C.F. >2

AC Current: Flexible Current Probe

  • Range: 2500 A
  • Resolution: 1 A (≤ 2500 A) 0.1 A (≤ 999.9 A)
  • Accuracy: 3 % ±5 digits (5 Hz to 500 Hz)

DC Current

  • Range 999.9: A
  • Resolution: 0.1 A
  • Accuracy: 2 % ±5 digits

AC Voltage: FieldSense

  • Range: 1000 V
  • Resolution: 1 V (≤ 1000 V)
  • Accuracy:
    • ≤ 4/0 AWG: 3 % ±5 digits (45 Hz to 66 Hz)
    • ≥ 4/0 AWG: 5 % ±5 digits (45 Hz to 66 Hz)

AC Voltage: Test Leads

  • Range: 600.0 V 1000 V
  • Resolution: 0.1 V (≤ 600.0 V); 1 V (≤ 1000 V)
  • Accuracy: 1 % ±5 digits (20 Hz to 500 Hz)

DC Voltage

  • Range: 600.0 V; 1000 V
  • Resolution: 0.1 V ≤ 600.0 V); 1 V (≤ 1000 V)
  • Accuracy: 1 % ± 5 digits

mV DC

  • Range: 500.0 mV
  • Resolution: 0.1 mV
  • Accuracy: 1 % ± 5 digits

Amps Frequency: Jaw

  • Range: 5.0 Hz to 500.0 Hz
  • Resolution: 0.1 Hz
  • Accuracy: 0.5 % ± 5 digits
  • Trigger level:
    • 5 Hz to 10 Hz, ≥ 10 A
    • 10 Hz to 100 Hz, ≥ 5 A
    • 100 Hz to 500 Hz, ≥ 10 A

Amps Frequency: Flexible Current Probe

  • Range: 5.0 Hz to 500.0 Hz
  • Resolution: 0.1 Hz
  • Accuracy: 0.5 % ±5 digits
  • Trigger level:
    • 5 Hz to 20 Hz, ≥ 25 A
    • 20 Hz to 100 Hz, ≥ 20 A
    • 100 Hz to 500 Hz, ≥ 25 A

Resistance

  • Range:
    • 60.00 kΩ
    • 6000 Ω
    • 600.0 Ω
  • Resolution:
    • 0.1 Ω (≤ 600.0 Ω)
    • 1 Ω (≤ 6000 Ω)
    • 10 Ω (≤ 60.00 kΩ)
  • Accuracy: 1 % ±5 digits

Capacitance

  • Range: 1000 μF
  • Resolution: 0.1 μF (≤ 100.0 μF); 1 F (≤ 1000 μF)
  • Accuracy: 1 % ±4 digits

Environmental

  • Operating temperature: -10 °C to 50 °C
  • Storage temperature: -40 °C to 60 °C
  • Operating Humidity (without condensation):
  • Non condensing (<10 °C)
  • ≤ 90 % RH (10 °C to 30 °C)
  • ≤ 75 % RH (30 °C to 40 °C)
  • ≤ 45 % RH (40 °C to 50 °C)
  • Temperature coefficients: Add 0.1 x specified accuracy for each degree C >28 °C or <18 °C
  • Ingress protection: IEC 60529: IP30 (jaw closed)
  • Operating altitude: 2000 m
  • Storage altitude: 12 000 m

Safety

  • General: IEC 61010-1: Pollution degree 2
  • Measurement: IEC 61010-2-032: CAT III 1000 V / CAT IV 600 V; IEC 61010-2-033: CAT III 1000 V / CAT IV 600 V
  • Current clamp for leakage current measurements: IEC 61557-13: Class 2, ≤ 30 A/m

The Fluke 378 FC True-RMS Non-Contact Voltage Clamp Meter with Fluke Connect Compatibility, iFlex and PQ Indicator, 1000A AC/DC gives users accurate voltage and current measurements through the clamp jaw.

The 378 FC clamp meter includes a unique PQ function that senses power quality issues automatically, so that users can quickly determine if there is an upstream supply problem, or a downstream equipment problem.

The Fluke 378 FC True-RMS clamp meter uses FieldSense™ technology to make testing faster and safer, all without contacting a live conductor. Users get accurate voltage and current measurements through the clamp jaw.

The 378 FC will detect and display power quality issues, relating to current, voltage, power factor or any combination of the three. Now users can quickly determine if an upstream supply problem exists, or if there is a downstream equipment problem.

With Fluke Connect software users can remotely log, trend and monitor measurements to pinpoint intermittent faults. Fluke Connect also allows users to gather data as the basis for a preventive maintenance program.

Simply clip the black test lead to any electrical ground, put the clamp jaw around the conductor and see reliable, accurate voltage and current values on the display.

Fluke Connect: See it. Save it. Share it. All the facts, Right in the Field

Fluke Connect with ShareLive video call lets you stay in contact with your entire team without leaving the field. The Fluke Connect mobile app is available for Android and iOS and works with over 20 different Fluke products. Make the best decisions faster than ever before by viewing all temperature, mechanical, electrical and vibration measurements for each equipment asset in one place. Get started saving time and money by increasing your productivity.

Get on Google Play
Download on the App Store
More Information
Country of OriginUnited States
BrandFluke
Catalog5111812
ConditionNEW
UPC095969916615
Vendor AliasFLUKE-378 FC
  • 1 - Non-Contact Voltage True-RMS AC/DC Clamp Meter (378 FC)
  • 1 - Test Lead Set (TL224)
  • 1 - TwistGuard Test Probe Set (TP175)
  • 1 - Black Grounding Clip (AC285)
  • 1 - iFlex Flexible Current Probe, 18 inch (48 cm) (i2500-18)
  • 1 - ToolPak Magnetic Meter Hanger (TPAK)
  • 1 - Premium Carrying Case