Greenlee UCT-8
Underground Cable Fault Tester with Overhead Hook Probe, 8kV DC
Greenlee UCT-8
Underground Cable Fault Tester with Overhead Hook Probe, 8kV DC
The Greenlee UCT-8 (52083998) is an Underground Cable Fault Tester with an Overhead Hook Probe. The large LED displays results as an analog bar graph. The UCT-8 first alerts the user to AC voltage on the underground cable and charges the cable to a maximum voltage of 8kVDC. An internal high voltage resistor enables use on grounded Y systems up to 25kV.
- Use on cable lengths up to 1500 ft. long
- Measures AC voltage before converting to DC voltage tester
- Lightweight one-piece solution for underground cable fault testing
- Performs DC leakage current testing of de-energized, shielded underground primary cable
- Self-contained 8kV high voltage source powers the tester - no external power required
- Can be used on cable lengths up to 1500 ft. long
- Provides clear and simple test results on large LED display
- Shows analog bar graph and indication of good or faulted cable
- Increases safety by measuring AC voltage before converting to a DC voltage tester
- Easy to use with one button operation for all functions
- Ideal for field use with durable housing and heavy-duty coiled grounded cord
- Equipped with universal spline and shotgun stick connection (hot stick sold separately)
- Field replaceable 9V lithium battery with low battery indication
- Supplied with overhead hook probe
- Operating Voltage Range: 100V to 25kVAC line-to-ground
- Operating Frequency: 50/60Hz
- Test Voltage: 8kVDC
- Accuracy: AC voltage, 5% of reading
- Maximum Cable Length Tested: 1500 ft. (457 m)
- Digital Display: Reads AC kilovolts and displays DC leakage/discharge current as analog bar graph
The Greenlee UCT-8 (52083998) Underground Cable Fault Tester with Overhead Hook Probe, 8kV DC, is a lightweight one-piece solution for DC leakage current testing of de-energized shielded primary voltage underground cables. Test results are displayed on a large LED display.
The UCT-8 first alerts the user to the presence of AC voltage on the underground cable. After verifying the cable is completely de-energized, the UCT-8 charges the cable to a maximum voltage of 8kVDC. Cable leakage current is measured and shown on the front display as an analog bar graph. After several seconds, test results are shown as GOOD, HIGH LEAKAGE or FAULT. The UCT-8 then proceeds to discharge the connected cable and verifies when this discharge process is complete.
An internal high voltage resistor allows the UCT-8 to be used on grounded Y systems up to 25kV. The insulated ground cord connects to any system ground or neutral.
The UCT-8 can test 15kV, 1/0 XLPE cables up to 7,500 ft. in length. Higher voltage cables allow longer cable lengths and larger conductors will reduce maximum cable length. The maximum cable charging time for the longest cables is 35 seconds.
Country of Origin | United States |
---|---|
Brand | Greenlee |
Catalog | 52083998 |
Condition | NEW |
UPC | 783310081371 |
Vendor Alias | UCT-8 |
- 1 - Underground Cable Fault Tester (UCT-8)
- 1 - Overhead Brass Hook Probe (025-OLPS-5)
- 1 - Plastic Carrying Case (CS-UCT)