The Yokogawa EY200 Digital Earth Resistance Tester has an earth voltage range for precise 3-pole and simplified 2-pole earth voltage measurement. The 2-pole method is ideal for lead or iron water-pipes or objects with a known value of earth resistance. It comes with a soft carrying bag.

  • Use even under adverse weather conditions
  • Large, easy-to-read LCD digital display
  • Warns when earth resistance of auxiliary earth spikes exceeds permissible limit
This product is available for shipping to the US, Canada, and Puerto Rico only.
$680.00
This item ships FREE
  • Designed to safety standard IEC 61557
  • Reference to IEC 60529: Degrees of protection provided by enclosures (IP54)
  • Measurement can be made even under adverse weather conditions
  • Large, easy-to-read LCD digital display
  • 2P Test leads (for simplified measurement) has structure that both safety alligator clip and test probe are available
  • Warns when earth resistance of auxiliary earth spikes exceeds permissible limit
  • Convenient carrying soft bag for accessories etc
  • 3-Pole Earth Resistance Measurement (Precise Measurement)
  • Display: LCD Digital Display: 1999-count digital reading
  • Measuring Range: Earth Resistance: 2000Ω LSD: 0.01 to 1Ω
  • Earth Voltage: 200V
  • Accuracy:
    • Earth Resistance:
      • 20Ω range: ±2%rdg±0.1Ω
      • 200 Ω range: ±2%rdg±3dgt
      • 2000 Ω range: ±2%rdg3dgt
    • Earth Voltage: ±1%rdg±4dgt
  • Measuring Frequency: Approx. 820Hz
  • Measuring Current: Approx. 3mA (at 20Ω range)
  • Battery Life: Approx. 4.5hours (at 5 second measuring 3300 times)
  • Operating Temp. and Humidity: 0~40°C, 85%Rh or less

The Yokogawa EY200 Digital Earth Resistance Tester is for testing power distribution lines, in-house wiring system, electrical appliances, etc. It also has an earth voltage range for earth voltage measurement.

3-Pole Earth Resistance Measurement (Precise Measurement)

Connect the earth/ground electrode (E) and auxiliary spikes (P, C) to the main body using the accessory test lead. Put apart 5 to 10 m between E and P, and P and C, respectively. E, P, and C should be approximately in a line.

2-Pole Earth Resistance Measurement (simplified measurement)

A simplified 2-pole measuring method can be used if there is an almost perfectly earth/ground object such as a lead or iron water-pipe (plastic pipes cannot be used) or if there is an object with a known value of earth resistance, near the measurement site.

More Information
BrandYokogawa
ConditionNEW
Vendor AliasEY200
  • 1 - 3-pole Test Lead (98074)
  • 1 - Earth Spikes (98070)
  • 1 - 2-pole Test Lead Set (98075)
  • 1 - Soft Carrying Case (93041)
  • 1 - Shoulder Belt (99018)
  • 6 - AA (R6) Dry Cells
  • 1 - User Manual