AEMC DTR-8510
Digital Transformer Ratiometer, 90-240V, 50/60 Hz
The AEMC 8510 90-240V, 50/60 Hz Universal Supply Digital Transformer Ratiometer is easy-to-use and portable, designed for on-site testing of power, potential and current transformers. When connected to a non-energized transformer, the 8510 accurately measures primary to secondary turns ratio, while simultaneously displaying polarity and excitation current.
- Measures power transformers, VT/PTs and current transformer CT turns ratios
- Measures power transformers, VT/PTs and current transformer CT turns ratios
- Displays turn ratio, excitation current, winding polarity and % deviation from the nameplate values
- Internal NiMH battery packs provide up to 10 hours of continuous operation
- Universal voltage (90-240V supply, 50-60Hz) via external smart/fast battery charger; complete charge in less than 4 hours
- Tests performed by exciting the primary and reading the secondary; provides safer conditions for the operator
- Display warns of incorrect lead connection, reverse polarity, open and short circuits
- Easy connection and test setup; no calibration or balancing required
- Large dual display with adjustable contrast ensures clearer visibility in any lighting environment day or night
- Low battery indicator
- Includes 15 foot lead set and soft carrying bag
- Stores up to 10,000 test results in internal memory
- USB port facilitates configuring the instrument and downloading test results
- EN 61010-1; 50V CAT IV
- Includes DataView analysis software for programming, downloading, storing and report generation of test data
The DTR 8510 is an easy-to-use portable digital transformer turns ratiometer designed for on-site testing of power, potential and current transformers. When connected to a non-energized transformer, the DTR® Model 8510 accurately measures primary to secondary turns ratio, while simultaneously displaying polarity and excitation current.
The DTR® is fully automatic and uses an ANSI/IEEE compliant test method. No user calibration, range selection, hand cranking or tedious balancing is required. At each measurement, the DTR® automatically self-calibrates and checks for open windings/connections/circuit breakers, short circuits (excess excitation current), incorrect test lead placement, and reverse polarity. Measurements are displayed quickly and accurately.
Vendor Alias | 2136.50 |
---|---|
Catalog | 2136.50 |
UPC | 685338160062 |
Country of Origin | United States |
Brand | AEMC |
Condition | NEW |
- 1 - Rechargeable 12V NiMH battery
- 1 - Power Supply Cord
- 1 - DataView analysis software on CD Disc
- 1 - Test Lead Set
- 1 - Instruction Manual